UPS Gateway

Categories: ,

Description

This project consisted of two separate buildings on the same site. The main sort building has 2 wet sprinkler zones covering the entire building with 1-1/2″ fire hose valves throughout the warehouse space. The maintenance building has 1 wet sprinkler zone and 1 dry sprinkler zone covering the building. The sprinkler design density and remote area were calculated per the project specifications which were significantly more demanding than a traditional NFPA 13 design. We were also tasked with limiting the main sizes to a max of 4″ due to structural limitations.

Project Type

New Construction

Area of Application (sq. ft.)

50,000 to 75,000

Number of Stories

2

Number of Sprinklers

750 to 1,000

Number of Zones

4

Design Standards

NFPA 13

System Type(s)

Dry, Wet

Occupancy Classifications

0.30 over 2,500 S.F. per specifications, Ordinary

Water Source

Municipal Supply